THE PUMP-TIPE GAS ODORIZATION COMPLEX (TU U 26.5-41292924-002: 2018)

 

            The gas odorization complex is designed to supply micro doses in the gas flow, which served to the consumer, in order to impart a specific smell to natural gas and timely confirm its leakage.

The complex provides a pulsed supply of odorant to the gas, using a differential pressure formed by the metering pump, based on the values ​​of the gas flow rate and the flow rate of the odorant, while observing the required degree of gas odorization.

            In case of failure of the automatic odorizer, a backup (emergency) odorization unit is put into operation. Commissioning is carried out manually or automatically (by separate order).

Complex provides:

  • maintenance of the necessary degree of odorization
  • the automatic control and correction of each dose of odorant
  • the connection with the calculator gas flow
  • the automatic control of the technological parameters
  • conducting of hourly, daily and monthly archival information with recording ​​of the main parameters, the occurrence of abnormal situations and operator interventions
  • the introduction of the gas flow rate (constant) from the remote control unit for the odorization of the entered value, in the absence of communication with the computer gas flow
  • activation of emergency and warning alarm in case of abnormal situations:

 

— the lack of supply of odorant in the pipeline (AS);

                        — battery discharge (AS)

                        — mismatch between calculated and actual dose of odorant

— odorant flow sensor is faulty

— no communication with interface module

                        — maximum frequency of the pump work

— odorant level in the tank is low

                        — odorant level in the tank is high                        — odorant level sensor is defective                        — no signal from the flow meter                        — main power 220V is missing

 

 

  • automatic transfer to backup power in case of lack of main power

 

  • automatic charging of batteries, etc.

 

 

 

Main technical specifications

 

 

Parameter name

 

symbol  

Value

                                                                        Technological unit

 

Type of odorization installation   Automatic
Climatic modification according to  the State standard GOST 15150   U1
 Ambient temperature Minus 30 ÷50
 Relative humidity % 30 ÷80
 Vibration (frequency / amplitude) Hz / mm 25/0,1
 Degree of protection of the cabinet unit from

  external influences according to the State  

  standard GOST 14254

IP 54
 Installation location of the process unit Ех On the GDS site

(in explosive area)

 Dosing method   Injection
 Odorant supply to gas pipeline   Electromagnetic diaphragm pump (membrane material — stainless steel)
 Pump life, not less years 12
 Odorant flow meter availability   Yes
 Used odorants   Ethylmercaptan, C2H5SH or a mixture of natural mercaptans “СПМ-1”
 Odorization rate g/1000m3 By default 16 (customizable, according to the results of determining the intensity of the smell of gas in the networks of consumers)
The maximum consumption of the gas to be odorized at the odorization rate of 16 g / 1000 m3, depending on the version: nm3 / hour

 

20 000 m3/hour

85 000 m3/hour

125 000 m3/hour

225 000 m3/hour

400 000 m3/hour

 Maximum pressure at the injection point  

 (without changing the design and replacing  

 nodes)

МPа 1,6

5,5

Device for visual control of odorant supply to the gas pipeline Yes
  Dosing error, not more than % ±5
The type of used compounds, excluding the influence of seasonal temperature fluctuations Lock-connections (metal on metal with double crimp ring)
   Odorant filtration system     µm

 

Three stage:

1-coarse filter on the storage unit odorant

(served by 100 microns);

2- fine filter at the inlet of the metering pump

(served by 60  microns);

3- fine filter at the inlet of the flow meter

(served by 40 microns).

 

System flushing device Yes
  The diameter of the output pipeline DN Specified at the place of installation
Protection against overflow of storage capacity when refueling   Yes
  Odorant input device for gas pipeline with  

  attached stainless steel tubes

Ø, mm 8÷12
  Operating temperature of the technological unit °С Minus 30 … +55
Overall dimensions of the technological unit, not more mm 2080×1030×740
Weight of the technological unit, not more kg 150
 

Automatic control unit

 

 Operating temperature of the electronic control

 unit, depending on the version

°С 0 … +55

Minus 25 … +55

Relative humidity % 30 ÷80
 Vibration (frequency / amplitude) Hz / mm 25/0,1
 Degree of protection of the cabinet of the unit  

 from external influences according to the State

 standard GOST 14254

IP 54
 Location of the electronic control unit Ех In the explosion-proof room
 Modes of operation Automatic (proportional to the gas flow rate from the metering unit).
By constant (by manually entered gas flow consumption)
Application of industrial PLC with modular architecture   Yes
The applying of the modular structure of the control unit (the ability to replace individual modules, without replacing the entire controller)   Yes
Control voltage of the metering pump V DC 24
Communication signal with odorant flow meter   0…10V,  pulse signal
The interface of communication with the consumption of gas calculator Pulse signal or RS232, RS485 interfaces
Interface output for data transfer to the upper level system and protocol for communication with the upper level RS232 / RS485 Modbus TCP Protocol
 Odorant technology accounting function g (kg) Consumption / balance (hour, day, month, year)
 Storage of archival information in the non-

 volatile memory of the controller

Yes
 Archive of current information, not less hours 72
 Archive of accidents, not less     years 1
 Archive of interventions, not less years 1
 Transfer to the upper level of control of discrete

 output signals of the “dry contact” type

  «Normal work»,

«A warning»,

«Crash»

 Overall dimensions of the control unit, no more mm 800х600х300
 Weight of the control unit (without AB), no

 more

kg 20
Main and backup power unit
Operating temperature of the electronic control unit, depending on the version °С 0 … +55
  Relative humidity % 30 ÷80
 Vibration (frequency / amplitude) Hz / mm 25/0,1
Degree of protection of the cabinet of the unit from external influences according to State standard GOST 14254 IP 44
Location of the electronic control unit Ех In the explosion-proof room

 

Power supply voltage V ~220 +22-33
 Backup power voltage V =24
 Power consumption without heater / with heater W 20 / 420
 Operating time from backup power source

 (without heater), not less

hours 72
 Protection from the impulse overvoltage Yes
                                                            Backup (emergency) odorization unit
 Type of instalation   Backup
 Ambient temperature Minus 30 ÷50
 Relative humidity % 30 ÷80
 Vibration (frequency / amplitude) Hz / mm 25/0,1
Degree of protection of the cabinet of the unit from external influences according to State standard GOST 14254 IP 44
 Place of installation of backup odorization unit Ех            On the GDS site (in explosive area) 
 Dosing method   Hydrostatic 
 Maximum pressure at the odorant entry point MPa  1,6
 Standard capacity  liters  10
 Tare capacity Yes
Device for visual control of odorant supply to the gas pipeline Yes
Visual odorant level indicator in tank Yes
Automatic start-up, in case of failure of the technological unit Option
Automatic counting of dosed odorant   Option
  Overall dimensions of the backup odorization  block, no more than mm 2200×1500×1200
 Weight of backup odorization block, not more

 than

kg 200
Odorant Storage Unit
  Climatic modification according to State  standard GOST 15150   U1
Ambient temperature Minus 30 ÷50
Relative humidity % 30 ÷80
Vibration (frequency / amplitude) Hz / mm 25/0,1
Degree of protection of the cabinet of the unit from external influences according to State standard GOST 14254 IP 54
  Installation place of the technological unit Ех On the GDS site (in  explosive  area)
  Stainless steel odorant capacity Yes
 Odorant capacity liters Determined when ordering *
 Pressure in the storage tank odorant, not more MPa  0,05
 The presence of a gas pressure regulator Yes
 Odorant storage unit with a canopy or in a heat- insulated cabinet, with a non-pouring tray (not less than 2 mm thick) of above-ground   performance Yes
 Thermal protective coating storage container or

 placement in a stainless steel cabinet

Yes
 A set of quick-detachable joints for filling a

 storage tank with an odorant like CAMLOCK

Yes
Visual control of the odorant level in the tank Yes
Safety valve of odorant storage tank with discharge on the vaporizer Yes
Automatic odorant level alarm in the tank Yes
  Odorant vaporizer Yes
Additional information
The useful life of the control unit, not less years 12
The service life of the facility, not less years 12
1.        Mean operating time between failures of the

2.        facility, not less

hours 30000
Average service life, no less (subject to timely maintenance work) years 12
  Frequency of maintenance, not less years 2
  The recovery time of the complex is no more  

 (without taking into account the preparation

 time for the restoration work)

hours 8
 Generalized indicator of the reliability of the

 complex

Ро≥0,92…0,95

within the limits of probability values To≥0,95 … 0,99 fulfillment of production assignments

Availability in the free sale on the territory of Ukraine of any elements of the installation and automatic control unit Yes
Overall dimensions of the complex “GOK” mm 2080×1030×740
Mass of the “GOK” odorization complex (excluding containers), not more than kg 350

 

 

 

 

 

 

 

 

 

Completeness

 

 Equipment:

 

— Technological unit- Automatic control unit- Main and backup power unit- Backup (emergency) odorization block

— Odorant Storage Unit

— Spare parts kit (optional)

 

  Documentation:

 

— Technological passport block

— Passport automatic control unit

— Main and backup power supply passport- Block backup (emergency) passport odorization- Odorant Passport Storage Unit

— Spare parts kit list (supplied by separate order)

— Gas Odorization Complex «GOK» operation manual